B&R X67IF1121-1

RS232 and RS485/RS422 usable in parallel 2 digital channels, configurable as inputs or outputs 2 digital inputs Connection of barcode readers, ID systems and sensors on one module Serial interfaces (barcode scanners for example) are often scattered throughout systems. This interface module from the remote X67 system is the optimal choice for this area of application: RS232 and RS485/RS422 connection options directly where they are needed, distributed on the machine or system. In addition, there are digital inputs and outputs on the same module so that corresponding 24 V sensors/actuators can also be connected.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
Communication module1x RS232 or 1x RS485/RS422, 2 digital inputs, 2 digital channels configurable as inputs or outputs using software
General information
Diagnostics / OutputsYes, using LED status indicator and software
Diagnostics / I/O power supplyYes, using LED status indicator and software
Diagnostics / RS232Yes, using LED status indicator
Diagnostics / RS485/RS422Yes, using LED status indicator
Connection type / X2X LinkM12, B-coded
Connection type / Interfaces and inputs/outputs4x M12, A-coded
Connection type / I/O power supplyM8, 4-pin
Power consumption / Internal I/O2.4 W
Power consumption / X2X Link power supply0.75 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
Insulation voltage between channel and bus500 Veff
B&R ID code0xA90F
Sensor/Actuator power supply0.5 A summation current
Status indicatorsRS232, RS485/RS422, I/O function per channel, supply voltage, bus function
Interfaces
Interface IF1 / SignalRS232
Interface IF1 / Max. distance900 m
Interface IF1 / Transfer rateMax. 115.2 kbit/s
Interface IF1 / FIFO bufferSoftware
Interface IF1 / Handshake linesNo
Interface IF2 / SignalRS485/RS422
Interface IF2 / Max. distance1200 m
Interface IF2 / Transfer rateMax. 115.2 kbit/s
Interface IF2 / FIFO bufferSoftware
Interface IF2 / Terminating resistorIntegrated in module
I/O power supply
Power consumption / Sensor/Actuator power supplyMax. 12 W
Nominal voltage24 VDC
Voltage range18 to 30 VDC
Integrated protective functionReverse polarity protection
Sensor/Actuator power supply
VoltageI/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 AMax. 2 VDC
Summation currentMax. 0.5 A
Short-circuit proofYes
Digital inputs
Input filter / Hardware≤100 µs
Input filter / SoftwareDefault 0 ms, configurable between 0 and 25 ms in 0.2 ms intervals
Switching threshold / Low<5 V
Switching threshold / High>15 VDC
QuantityUp to 4 if the 2 digital channels are used as digital inputs
Nominal voltage24 VDC
Input characteristics per EN 61131-2Type 1
Input voltage18 to 30 VDC
Input current at 24 VDCTyp. 3.5 mA
Input circuitSink
Input resistanceTyp. 6.67 kΩ
Digital outputs
Switching delay / 0 → 1<100 μs
Switching delay / 1 → 0<150 μs
Switching frequency / Resistive loadMax. 1000 Hz
Switching frequency / Inductive loadSee section "Switching inductive loads".
QuantityUp to 2 if the 2 digital channels are used as digital outputs
VariantCurrent-sourcing FET
Nominal voltage24 VDC
Switching voltageI/O power supply minus residual voltage
Nominal output current0.5 A
Total nominal current1 A
Output circuitSource
Output protectionThermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off<120 μA
Peak short-circuit current<2.1 A
Switch-on in the event of overload shutdown or short-circuit shutdownApprox. 1 ms (depends on the module temperature)
Braking voltage when switching off inductive loadsTyp. 68 VDC
Electrical properties
Electrical isolationBus isolated from channel and IF Channel not isolated from channel and IF
Operating conditions
Mounting orientation / AnyYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP67
Ambient conditions
Temperature / Operation-25 to 60°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Mechanical properties
Dimensions / Width53 mm
Dimensions / Height85 mm
Dimensions / Depth42 mm
Torque for connections / M8Max. 0.4 Nm
Torque for connections / M12Max. 0.6 Nm
Weight195 g