B&R X67SI8103
8 safe digital inputs, sink circuit 2 pulse outputs - available on all 4 female connectors 2 standard inputs, sink circuit 2 standard outputs, source circuit Device supply Software input filter configurable for each channel Standardized 8-pin M12 device interface This module is equipped with 8 safe digital inputs. They are designed for a nominal voltage of 24 VDC. The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3. The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 2x M12 interface each with 2 safe type A digital inputs and 2 pulse outputs, 24 VDC, 2x standardized 8-pin M12 device interface each with 1 digital input without safety function and 2 safe type A digital inputs and 2 pulse outputs, 24 VDC and 1 digital output without safety function, 24 VDC, 0.6 A and 1 device power supply, 24 VDC, 2 A |
General information
| Diagnostics / Module run/error | Yes, using LED status indicator and software |
| Diagnostics / I/O function | Yes, using LED status indicator and software |
| Blackout mode / Scope | Module |
| Blackout mode / Function | Module functionality |
| Blackout mode / Standalone mode | No |
| Connection type / X2X Link | M12, B-coded |
| Connection type / Inputs/Outputs | M12 8-pin or M12 5-pin, A-coded |
| Connection type / I/O power supply | M8, 4-pin |
| Power consumption / Bus | 0.9 W |
| Power consumption / Internal I/O | 2.1 W |
| Additional power dissipation caused by actuators (resistive) [W] / Digital outputs | 0.216 |
| Additional power dissipation caused by actuators (resistive) [W] / Pulse outputs | 0.192 |
| Electrical isolation / Channel - Bus | Yes |
| Electrical isolation / Channel - Channel | No |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| Certifications / Functional safety | cULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013 |
| Certifications / Functional safety #2 | IEC 61508, up to SIL 3 IEC 62061, up to SIL 3 ISO 13849-1, up to Cat. 4 / PL e IEC 61511, up to SIL 3 |
| Certifications / Functional safety #3 | EN 50156-1 |
| Certifications / ATEX | Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Certifications / HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Certifications / KC | Yes |
| B&R ID code | 0xBB7C |
| Status indicators | I/O function per channel, operating state, module status |
Safety characteristics
| Note | See section "Safety characteristics". |
24 VDC output
| Output voltage | 24 VDC -15% / +20% |
| Output current | 2 A |
I/O power supply
| Nominal voltage | 24 VDC |
| Voltage range | 18 to 30 VDC |
| Integrated protective function | Reverse polarity protection |
Digital inputs
| Input filter / Hardware | ≤150 μs |
| Switching threshold / Low | <5 VDC |
| Switching threshold / High | >15 VDC |
| Quantity | 2 |
| Nominal voltage | 24 VDC |
| Input characteristics per EN 61131-2 | Type 1 |
| Input voltage | 24 VDC -15% / +20% |
| Input current at 24 VDC | Min. 2 mA to max. 7.24 mA |
| Input circuit | Sink |
| Input resistance | Min. 3.3 kΩ |
| Insulation voltage between channel and bus | 500 Veff |
Safe digital inputs
| Input filter / Hardware | ≤150 μs |
| Input filter / Software | Configurable between 0 and 500 ms |
| Switching threshold / Low | <5 VDC |
| Switching threshold / High | >15 VDC |
| Quantity | 8 |
| Variant | Type A |
| Nominal voltage | 24 VDC |
| Input characteristics per EN 61131-2 | Type 1 |
| Input circuit | Sink |
| Input voltage | 24 VDC -15% / +20% |
| Input current at 24 VDC | Min. 2 mA to max. 8.28 mA |
| Input resistance | Min. 2.9 kΩ |
| Error detection time | 200 ms |
| Insulation voltage between channel and bus | 500 Veff |
| Line length between signal source (pulse output or external signal) and input | Max. 60 m with unshielded line Max. 400 m with shielded line |
Digital outputs
| Quantity | 2 |
| Variant | FET, positive switching, output level readable |
| Nominal voltage | 24 VDC |
| Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
| Max. switching frequency | See section "Inrush current behavior for output channels". |
| Nominal output current | 0.6 A |
| Total nominal current | 1.2 A |
| Output protection | See section "Inrush current behavior for output channels". |
| Leakage current when the output is switched off | <500 μA |
| RDS(on) | 300 mΩ |
| Peak short-circuit current | See section "Inrush current behavior for output channels". |
| Braking voltage when switching off inductive loads | 50 VDC |
| Insulation voltage between channel and bus | 500 Veff |
| Max. capacitive load | 100 nF |
| Peak output current | 1 A |
Pulse outputs
| Quantity | 8 |
| Variant | Push-Pull |
| Nominal output current | 40 mA |
| Output protection | Shutdown of individual channels in the event of overload or short circuit |
| Peak short-circuit current | 25 A for 15 µs |
| Short-circuit current | 100 mAeff |
| Leakage current when the output is switched off | 0.1 mA |
| RDS(on) | 60 Ω |
| Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
| Total nominal current | 80 mA |
Operating conditions
| Mounting orientation / Any | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP67 |
Ambient conditions
| Temperature / Operation | -40 to 60°C |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
Mechanical properties
| Dimensions / Width | 53 mm |
| Dimensions / Height | 85 mm |
| Dimensions / Depth | 42 mm |
| Torque for connections / M8 | Max. 0.4 Nm |
| Torque for connections / M12 | Max. 0.6 Nm |
| Weight | 190 g |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
3D CAD models
Certificates
- 2226379 CSA Certificate of Compliance X20 X67
- E115267 UL CoC X67
- EU Data Act - X20-X67 SafeIO - Connected Product Information Notice
- EU Declaration FS PLC X67
- FS EN 50156 Zertifikat SafeLOGIC, SafeIO
- M6A 041745 0010 TÜV Süd FS Certificate SafeDESIGNER, SafeLOGIC, SafeIO
- M6A 041745 0013 TÜV Süd FS Certificate mapp Safety
- M6A 041745 0023 TÜV Süd FS Certificate Safety+
- TÜV 05 ATEX 7201 X
- UK Declaration FS PLC X67
- X20, X67 KC certificates
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.