B&R X67UM1352
1 strain gauge input with 24-bit resolution High data output rate (10 to 3,750 Hz) Adjustable gain 1 high-side output 24 VDC, 0.5 A 1 high-side output 24 VDC, 1.0 A This module is used for the decentralized connection of a force sensor using strain gauge with a converter resolution up to 24 bits. The module is also equipped with 4 digital inputs and 2 digital outputs.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 4 digital inputs, 2 digital outputs, 1 input for full-bridge strain gauge |
General information
| Diagnostics / Outputs | Yes, using LED status indicator |
| Diagnostics / I/O power supply | Yes, using LED status indicator and software |
| Connection type / X2X Link | M12, B-coded |
| Connection type / Inputs/Outputs | 4x M12, A-coded |
| Connection type / I/O power supply | M8, 4-pin |
| Power consumption / Internal I/O | 1 W |
| Power consumption / X2X Link power supply | 0.75 W |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| Certifications / ATEX | Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Certifications / HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Certifications / KC | Yes |
| B&R ID code | 0x1CDF |
| Status indicators | I/O function per channel, supply voltage, bus function |
I/O power supply
| Power consumption / Sensor power supply | Max. 12 W |
| Nominal voltage | 24 VDC ±25% |
| Integrated protective function | Reverse polarity protection |
Strain gauge supply
| Voltage | 4.422 VDC / max. 60 mA |
| Voltage drop for short-circuit protection at 60 mA | Max. 0.36 VDC |
| Short-circuit proof | Yes |
Sensor/Actuator power supply
| Voltage | I/O power supply minus voltage drop for short-circuit protection |
| Voltage drop for short-circuit protection at 0.5 A | Max. 2 VDC |
| Summation current | Max. 0.5 A |
| Short-circuit proof | Yes |
Full-bridge strain gauge
| Input filter / Cutoff frequency | 50 kHz |
| Input filter / Order | 1 |
| Input filter / Slope | 20 dB |
| Output of digital value / Broken bridge supply line | Value approaching 0 |
| Output of digital value / Broken sensor line | Value approaching ±final value |
| Output of digital value / Valid range of values | 0x7FFF FFFF to 0x8000 0001 |
| Strain gauge supply / Voltage | 4.5 VDC / max. 60 mA |
| Strain gauge supply / Connection | 4-wire connections |
| Strain gauge supply / Short-circuit and overload-proof | Yes |
| Quantization / LSB value (16-bit) / 69 mV/V | 9.31 µV |
| Quantization / LSB value (16-bit) / 138 mV/V | 18.6 µV |
| Quantization / LSB value (16-bit) / 276 mV/V | 37.3 µV |
| Quantization / LSB value (16-bit) / 553 mV/V | 74.6 µV |
| Quantization / LSB value (24-bit) / 69 mV/V | 36.4 nV |
| Quantization / LSB value (24-bit) / 138 mV/V | 72.8 nV |
| Quantization / LSB value (24-bit) / 276 mV/V | 146.0 nV |
| Quantization / LSB value (24-bit) / 553 mV/V | 251.0 nV |
| Strain gauge factor | ±15.625 to ±125 mV/V, configurable using software |
| Input type | Differential, used to evaluate a full-bridge strain gauge |
| Digital converter resolution | 24-bit |
| Conversion time | Depends on the configured data output rate |
| Data output rate | 10 to 3750 samples per second, configurable using software |
| Operating range / Measurement sensor | 75 to 5000 Ω |
| Influence of cable length | Twisted and shielded conductors, cable length as short as possible, cable routing separate from load circuits, without intermediate terminal to sensor |
| Input protection | RC protection |
| Input current | 450 nA |
| Common-mode range | 0 to 3 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on the inputs "Input +" and "Input -" |
| Insulation voltage between input and bus | 500 Veff |
| Gain | 1 to 8, configurable using software |
| Conversion procedure | Sigma-delta |
| Temperature coefficient | 50 ppm/°C |
Digital inputs
| Input filter / Hardware | <1 ms |
| Input filter / Software | - |
| Switching threshold / Low | <5 VDC |
| Switching threshold / High | >15 VDC |
| Quantity | 4 |
| Nominal voltage | 24 VDC |
| Input characteristics per EN 61131-2 | Type 1 |
| Input voltage | 24 VDC ±25% |
| Input current at 24 VDC | Typ. 5 mA |
| Input circuit | Sink |
| Input resistance | Typ. 4.27 kΩ |
| Sensor power supply | 0.5 A summation current |
| Insulation voltage between channel and bus | 500 Veff |
Digital outputs
| Nominal output current / Output 1 | 0.5 A |
| Nominal output current / Output 2 | 1 A |
| Switch-on time of output driver / Output 1 / Typical | 50 µs |
| Switch-on time of output driver / Output 1 / 0 → 1 (90% VOut) | Max. 100 µs |
| Switch-on time of output driver / Output 2 / Typical | 60 µs |
| Switch-on time of output driver / Output 2 / 0 → 1 (90% VOut) | Max. 160 µs |
| Switch-off time of output driver / Output 1 / Typical | 75 µs |
| Switch-off time of output driver / Output 1 / 1 → 0 (90% VOut) | Max. 150 µs |
| Switch-off time of output driver / Output 2 / Typical | 15 µs |
| Switch-off time of output driver / Output 2 / 1 → 0 (90% VOut) | Max. 50 µs |
| Braking voltage when switching off inductive loads / Output 1 | -47 VDC |
| Braking voltage when switching off inductive loads / Output 2 | Approx. 1 VDC |
| Max. frequency / Output 1 | 100 Hz |
| Max. frequency / Output 2 | 1 kHz |
| Quantity | 2 |
| Nominal voltage | 24 VDC |
| Switching voltage | 24 VDC ±25% |
| Output circuit | Source |
| Output protection | Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply |
| Actuator power supply | External |
| Insulation voltage between output and bus | 500 Veff |
Electrical properties
| Electrical isolation | Channel isolated from bus and digital isolated from analog Digital not isolated from I/O power supply |
Operating conditions
| Mounting orientation / Any | Yes |
| Installation elevation above sea level / 0 to 2000 m | No limitation |
| Installation elevation above sea level / >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP67 |
Ambient conditions
| Temperature / Operation | -25 to 60°C |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
Mechanical properties
| Dimensions / Width | 53 mm |
| Dimensions / Height | 85 mm |
| Dimensions / Depth | 42 mm |
| Torque for connections / M8 | Max. 0.4 Nm |
| Torque for connections / M12 | Max. 0.6 Nm |
| Weight | 200 g |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
3D CAD models
ECAD / EPLAN
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.