IAC

B&R X90AISG0.02-00

9 to 32 VDC 2 full-bridge strain gauge inputs Data output rate configurable from 2.5 Hz to 7.5 kHz Special operating modes (synchronous mode and multisampling) Configurable filter level This module is equipped with 2 inputs for evaluating full-bridge strain gauges and works with 4-wire and 6-wire strain gauge load cells. The concept applied by the module requires compensation in the measurement system. This compensation eliminates the absolute uncertainty in the measurement circuit, such as component tolerances, effective bridge voltage or zero offset. The measurement precision refers to the absolute (compensated) value, which will only change as a result of changes in the operating temperature. Communication to the mainboard is made possible via X2X Link.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module2 full-bridge strain gauge inputs
General information
Certifications / UN ECE-R10Yes
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
B&R ID code0xF79D
Status indicators-
Multi-function inputs
Multifunction analog inputs (MF-AI) / Quantity2
Multifunction analog inputs (MF-AI) / FunctionsAnalog input, 24-bit digital converter resolution
Full-bridge strain gauge
Input filter / Cutoff frequency5 kHz
Input filter / Order3
Input filter / Slope60 dB
Output of digital value / Broken bridge supply lineValue approaching 0
Output of digital value / Broken sensor lineValue approaching ±end value (status bit "Line monitoring" is set in register "Module status")
Output of digital value / Valid range of values0xFF800001 to 0x007FFFFF (-8,388,607 to 8,388,607)
Strain gauge supply / Voltage5.5 VDC / Max. 65 mA
Strain gauge supply / Short-circuit and overload-proofYes
Strain gauge supply / Voltage drop for short-circuit protectionMax. 0.2 VDC at 65 mA and 25°C
Quantization / LSB value (16-bit) / 2 mV/V336 nV
Quantization / LSB value (16-bit) / 4 mV/V671 nV
Quantization / LSB value (16-bit) / 8 mV/V1.343 μV
Quantization / LSB value (16-bit) / 16 mV/V2.686 μV
Quantization / LSB value (16-bit) / 32 mV/V5.371 μV
Quantization / LSB value (16-bit) / 64 mV/V10.74 μV
Quantization / LSB value (16-bit) / 128 mV/V21.48 μV
Quantization / LSB value (16-bit) / 256 mV/V42.97 μV
Quantization / LSB value (24-bit) / 2 mV/V1.31 nV
Quantization / LSB value (24-bit) / 4 mV/V2.62 nV
Quantization / LSB value (24-bit) / 8 mV/V5.25 nV
Quantization / LSB value (24-bit) / 16 mV/V10.49 nV
Quantization / LSB value (24-bit) / 32 mV/V20.98 nV
Quantization / LSB value (24-bit) / 64 mV/V41.96 nV
Quantization / LSB value (24-bit) / 128 mV/V83.92 nV
Quantization / LSB value (24-bit) / 256 mV/V167.85 nV
Strain gauge factor2 to 256 mV/V, configurable using software
Connection4- or 6-wire connections
Input typeDifferential, used to evaluate a full-bridge strain gauge
Digital converter resolution24-bit
Conversion timeDepends on the configured data output rate
Data output rate2.5 to 7,500 samples per second, configurable using software (fDATA)
ADC filter characteristicsSigma-delta, see section "Filter characteristics of the sigma-delta A/D converter"
Operating range / Measurement sensor85 to 5,000 Ω
Influence of cable lengthSee section "Calculation example", sensor cable length: Max. 30 m
Input protectionRC protection
Common-mode range0 to 3 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on inputs "Input +" and "Input -"
Conversion procedureSigma-delta
Max. gain drift12 ppm/°C
Max. offset drift2 ppm/°C
Nonlinearity<10 ppm
Operating conditions
Mounting orientation / AnyYes
Chemical resistanceNot guaranteed
Degree of protection per EN 60529Up to IP66
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-40 to 85°C housing surface
Temperature / Operation / Vertical mounting orientation-40 to 85°C housing surface
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 100%, condensing
Relative humidity / Storage5 to 100%, condensing
Relative humidity / Transport5 to 100%, condensing
Shock / OperationFor shock test 50 g, 11 ms analog values out of tolerance
Mechanical properties
Dimensions / Width47 mm
Dimensions / Length95 mm
Torque for connections / M120.6 Nm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.