B&R X90RO440.04-S1

9 to 32 VDC 4 safe relay outputs Output type "Relay" Nominal output current 2x 2 A and 2x 4 A Normally open contact Single-channel isolated outputs X2X Link The relay option board provides 4 additional safe relay outputs. Communication to the mainboard is made possible via X2X Link. The modules can be used for controlling floating actuators in safety-related applications up to PL e or SIL 3. Safety relays are installed within the module. The positively driven feedback contacts are evaluated within the module. The safe digital output modules have a start interlock on error in the event of network errors.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module4 relays with 1 normally open contact each, 9 to 32 VDC / 2 and 4 A
General information
System requirements / Automation Studio4.7 or later
System requirements / Automation Runtime4.7 or later
System requirements / mapp Technology Packagemapp Safety 5.12 and later:
Diagnostics / Module run/errorYes, using software
Diagnostics / OutputsYes, using software
Power consumption / Bus0.26 W
Power consumption / Internal I/O1.65 W
Certifications / UN ECE-R10Yes
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
B&R ID code0xFB3D
Status indicators-
Power consumptionMax. 2 W
Max. I/O cycle time1 ms
Additional power dissipation caused by actuators (resistive) [W]+3.2
Safety characteristics
EN ISO 13849-1:2015 / MTTFD per channel100 years if the relay channel is used individually, 390 years if 2 relay channels are connected in series
EN ISO 13849-1:2015 / Mission timeMax. 20 years
IEC 61508:2010, EN 62061:2013 / PFH / PFHd / Module<2.7*10⁻⁷ if the relay channel is used individually, <5.4*10⁻⁹if 2 relay channels are connected in series
IEC 61508:2010, EN 62061:2013 / PFH / PFHd / openSAFETY wiredNegligible
IEC 61508:2010, EN 62061:2013 / PFH / PFHd / openSAFETY wireless<1*10⁻¹⁴ * Number of openSAFETY packets per hour
IEC 61508:2010, EN 62061:2013 / PFD per channel<5.6*10⁻⁴ if the relay channel is used individually, <1*10⁻⁴if 2 relay channels are connected in series
IEC 61508:2010, EN 62061:2013 / Proof test interval (PT)20 years
Safe relay channels / EN ISO 13849-1:2015 / B10d / DC1, 24 VDC2 A / 1,800,000 4 A / 1,000,000
Safe relay channels / EN ISO 13849-1:2015 / B10d / DC13, 24 VDC2 A / 121,400 4 A / 120,000
Safe relay channels / EN ISO 13849-1:2015 / CategoryKAT 1 if the relay channel is used individually, KAT 4 if 2 relay channels are connected in series
Safe relay channels / EN ISO 13849-1:2015 / PLPL c if the relay channel is used individually, PL e if 2 relay channels are connected in series
Safe relay channels / IEC 61508:2010, EN 62061:2013 / SIL CLSIL 1 if the relay channel is used individually, SIL 3 if 2 relay channels are connected in series
I/O power supply
Voltage range9 to 32 VDC
Relay outputs
Switching delay / 0 → 1<50 ms
Switching delay / 1 → 0<20 ms
Service life / MechanicalMin. 1 x 10⁷ ops.
Service life / ElectricalMin. 1 x 10⁵ ops. (at 4 A / 32 VDC)
Protective circuit / Internal-
Protective circuit / ExternalRelays 1 and 2: External fuse 2 A Relays 3 and 4: External fuse 4 A
Max. switching capacity / DC1Relays 1 and 2: 24 VDC / 2 A Relays 3 and 4: 24 VDC / 4 A
Max. switching capacity / DC13Relays 1 and 2: 24 VDC / 2 A Relays 3 and 4: 24 VDC / 4 A
Quantity4
VariantRelay / Normally open contact, internal high-side and low-side control
Nominal output currentRelays 1 and 2: 2 A Relays 3 and 4: 4 A
Diagnostic statusContact position determined by positively driven contacts
Max. switching frequency10 Hz
Contact resistance (without terminal block)80 mΩ
Contact service lifeSee "Contact service life".
Switching voltage range5 to 32 VDC
Switching current range1 mA to 4 A
Max. inrush current20 A for 25 ms, max. 1x per minute
Overvoltage category per EN 60664-1II
Electrical properties
Electrical isolationChannel isolated from channel and bus
Operating conditions
Mounting orientation / AnyYes
Degree of protection per EN 60529IP66, IP69K
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-40 to 75°C housing surface
Temperature / Operation / Vertical mounting orientation-40 to 75°C housing surface
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 100%, condensing
Relative humidity / Storage5 to 100%, condensing
Relative humidity / Transport5 to 100%, condensing
Mechanical properties
Dimensions / Width47 mm
Dimensions / Length95 mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.