B&R X90RO440.04-S1
9 to 32 VDC 4 safe relay outputs Output type "Relay" Nominal output current 2x 2 A and 2x 4 A Normally open contact Single-channel isolated outputs X2X Link The relay option board provides 4 additional safe relay outputs. Communication to the mainboard is made possible via X2X Link. The modules can be used for controlling floating actuators in safety-related applications up to PL e or SIL 3. Safety relays are installed within the module. The positively driven feedback contacts are evaluated within the module. The safe digital output modules have a start interlock on error in the event of network errors.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 4 relays with 1 normally open contact each, 9 to 32 VDC / 2 and 4 A |
General information
| System requirements / Automation Studio | 4.7 or later |
| System requirements / Automation Runtime | 4.7 or later |
| System requirements / mapp Technology Package | mapp Safety 5.12 and later: |
| Diagnostics / Module run/error | Yes, using software |
| Diagnostics / Outputs | Yes, using software |
| Power consumption / Bus | 0.26 W |
| Power consumption / Internal I/O | 1.65 W |
| Certifications / UN ECE-R10 | Yes |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| B&R ID code | 0xFB3D |
| Status indicators | - |
| Power consumption | Max. 2 W |
| Max. I/O cycle time | 1 ms |
| Additional power dissipation caused by actuators (resistive) [W] | +3.2 |
Safety characteristics
| EN ISO 13849-1:2015 / MTTFD per channel | 100 years if the relay channel is used individually, 390 years if 2 relay channels are connected in series |
| EN ISO 13849-1:2015 / Mission time | Max. 20 years |
| IEC 61508:2010, EN 62061:2013 / PFH / PFHd / Module | <2.7*10⁻⁷ if the relay channel is used individually, <5.4*10⁻⁹if 2 relay channels are connected in series |
| IEC 61508:2010, EN 62061:2013 / PFH / PFHd / openSAFETY wired | Negligible |
| IEC 61508:2010, EN 62061:2013 / PFH / PFHd / openSAFETY wireless | <1*10⁻¹⁴ * Number of openSAFETY packets per hour |
| IEC 61508:2010, EN 62061:2013 / PFD per channel | <5.6*10⁻⁴ if the relay channel is used individually, <1*10⁻⁴if 2 relay channels are connected in series |
| IEC 61508:2010, EN 62061:2013 / Proof test interval (PT) | 20 years |
| Safe relay channels / EN ISO 13849-1:2015 / B10d / DC1, 24 VDC | 2 A / 1,800,000 4 A / 1,000,000 |
| Safe relay channels / EN ISO 13849-1:2015 / B10d / DC13, 24 VDC | 2 A / 121,400 4 A / 120,000 |
| Safe relay channels / EN ISO 13849-1:2015 / Category | KAT 1 if the relay channel is used individually, KAT 4 if 2 relay channels are connected in series |
| Safe relay channels / EN ISO 13849-1:2015 / PL | PL c if the relay channel is used individually, PL e if 2 relay channels are connected in series |
| Safe relay channels / IEC 61508:2010, EN 62061:2013 / SIL CL | SIL 1 if the relay channel is used individually, SIL 3 if 2 relay channels are connected in series |
I/O power supply
| Voltage range | 9 to 32 VDC |
Relay outputs
| Switching delay / 0 → 1 | <50 ms |
| Switching delay / 1 → 0 | <20 ms |
| Service life / Mechanical | Min. 1 x 10⁷ ops. |
| Service life / Electrical | Min. 1 x 10⁵ ops. (at 4 A / 32 VDC) |
| Protective circuit / Internal | - |
| Protective circuit / External | Relays 1 and 2: External fuse 2 A Relays 3 and 4: External fuse 4 A |
| Max. switching capacity / DC1 | Relays 1 and 2: 24 VDC / 2 A Relays 3 and 4: 24 VDC / 4 A |
| Max. switching capacity / DC13 | Relays 1 and 2: 24 VDC / 2 A Relays 3 and 4: 24 VDC / 4 A |
| Quantity | 4 |
| Variant | Relay / Normally open contact, internal high-side and low-side control |
| Nominal output current | Relays 1 and 2: 2 A Relays 3 and 4: 4 A |
| Diagnostic status | Contact position determined by positively driven contacts |
| Max. switching frequency | 10 Hz |
| Contact resistance (without terminal block) | 80 mΩ |
| Contact service life | See "Contact service life". |
| Switching voltage range | 5 to 32 VDC |
| Switching current range | 1 mA to 4 A |
| Max. inrush current | 20 A for 25 ms, max. 1x per minute |
| Overvoltage category per EN 60664-1 | II |
Electrical properties
| Electrical isolation | Channel isolated from channel and bus |
Operating conditions
| Mounting orientation / Any | Yes |
| Degree of protection per EN 60529 | IP66, IP69K |
Ambient conditions
| Temperature / Operation / Horizontal mounting orientation | -40 to 75°C housing surface |
| Temperature / Operation / Vertical mounting orientation | -40 to 75°C housing surface |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
| Relative humidity / Operation | 5 to 100%, condensing |
| Relative humidity / Storage | 5 to 100%, condensing |
| Relative humidity / Transport | 5 to 100%, condensing |
Mechanical properties
| Dimensions / Width | 47 mm |
| Dimensions / Length | 95 mm |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
- Integrated safety technology user's manual(de)
- Integrated safety technology user's manual(it)
- Integrated safety technology user's manual(fr)
- Integrated safety technology user's manual(en)
- X90 mobile System User´s Manual(de)
- X90 mobile System User´s Manual(it)
- X90 mobile System User´s Manual(fr)
- X90 mobile System User´s Manual(en)
Certificates
- EU Data Act - X90 - Connected Product Information Notice
- EU Declaration FS mobile automation X90
- EU Declaration Industrial sector X90
- EU Declaration Mobile machinery X90
- M6A 041745 0013 TÜV Süd FS Certificate mapp Safety
- M6A 041745 0015 TÜV Süd FS Certificate X90 mobile
- UK Declaration Industrial sector X90
- UN ECE-R10
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.