VFD Cross-Reference
Enter a variable frequency drive model number and see candidate equivalents across 12 brands (4,034 drives indexed) — matched on voltage class, standard power rating, and overload duty, from official manufacturer ratings tables. Or size a drive from your motor nameplate below. IAC is an authorized distributor for Benshaw, Invertek, LS Electric and Toshiba.
Invertek equivalents (6)
- ODP-2-62030-3KF42-MNODP-2 · 30 kW · 110 A · IP20
- ODP-2-62040-3HF42-MNODP-2 · 40 HP · 110 A · IP20
- ODV-3-621100-3F12-MNODV-3 · 30 kW · 40 HP · 110 A · IP20
- ODP-2-62030-3KF4N-MNODP-2 · 30 kW · 110 A · IP55
- ODP-2-62040-3HF4N-MNODP-2 · 40 HP · 110 A · IP55
- ODV-3-621100-3F1N-MNODV-3 · 30 kW · 40 HP · 110 A · IP55
Toshiba equivalents (1)
- VFAS3-2300PVF-AS3 · 30 kW · 40 HP · 123 A · IP20 · heavy duty · 908×265×313 mm, 57.6 kg
Benshaw equivalents (2)
- VFD-RSI-040-H2-2CRSi H2 · 30 kW · 40 HP · 110 A · IP20 · normal duty · 510×325×284 mm, 32.9 kgnormal duty — verify overload sizing
- RSi-040-SG-2BRSi SG · 30 kW · 40 HP · 115 A · NEMA1 · normal dutynormal duty — verify overload sizing
ABB equivalents (2)
- ACS550-01-114A-2ACS550 · 30 kW · 40 HP · 114 A · IP21 · normal duty · 596×203×262 mm, 24 kgnormal duty — verify overload sizing
- ACS550-U1-114A-2ACS550 · 30 kW · 40 HP · 114 A · NEMA1 · normal duty · 596×203×262 mm, 24 kgnormal duty — verify overload sizing
Fuji Electric equivalents (3)
- FRN0146G2S-2GFRENIC-MEGA (G2) · 30 kW · 40 HP · 119 A · IP00 · heavy duty · 550×320×255 mm, 23 kg
- FRN050G1H-2UFRENIC-MEGA (G1H) · 40 HP · 119 A · IP00 · heavy duty · 550×320×255 mm, 31 kg
- FRN050G1S-2UFRENIC-MEGA (G1S) · 40 HP · 119 A · IP00 · heavy duty · 550×320×255 mm, 25 kg
WEG equivalents (7)
- CFW500G0145T2DB20G2CFW500-G2 · 40 HP · 115 A · IP20 · heavy duty · 675.6×335.3×315 mm, 51.98 kg
- CFW500G0145T2NB20G2CFW500-G2 · 40 HP · 115 A · IP20 · heavy duty · 675.6×335.3×315 mm, 51.98 kg
- CFW900D0135T2DB20Y2BCFW900 · 40 HP · 110 A · IP20 · heavy duty · 624.8×248.9×294.6 mm, 33.48 kg
- CFW900D0135T2NB20Y2BCFW900 · 40 HP · 110 A · IP20 · heavy duty · 624.8×248.9×294.6 mm, 33.48 kg
- CFW110142T2O55DSZCFW11 · 40 HP · 115 A · IP55 · heavy duty · 1000.8×429.3×388.6 mm, 96.03 kg
- CFW110142T2ON1DBZCFW11 · 40 HP · 115 A · NEMA1 · heavy duty · 675.6×335.3×358.1 mm, 65.32 kg
- CFW110142T2ON1ZCFW11 · 40 HP · 115 A · NEMA1 · heavy duty · 675.6×335.3×358.1 mm, 65.32 kg
Mitsubishi equivalents (2)
- FR-A820-01540FR-A800 · 30 kW · 115 A · IP00 · heavy duty · 550×325×195 mm, 22 kg
- FR-F720-30KFR-F700 · 30 kW · 114 A · IP00 · normal duty · 400×250×190 mm, 14 kgnormal duty — verify overload sizing
Candidate matches by voltage class, standard power step and duty; the footprint badge means the candidate fits within the source drive envelope (width and height, ±2 mm, from official dimension tables) — always confirm control features, I/O, and dimensions against the datasheets before substituting. Sources: official manufacturer ratings tables.
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs Yaskawa parts — new, refurbished, or exchange units with warranty.
Don't have a drive model? Size from the motor.
Enter nameplate values (or photograph the plate). We size on continuous current (FLA × service factor × duty margin), then list matching VFDs — authorized brands first.
Motor sizing FAQ
- What do I read on the nameplate?
- Look for horsepower (HP) or kilowatts (kW), full-load amps (FLA or rated current), supply voltage, and service factor (SF). FLA is the most reliable gate for drive current — use it when it is printed.
- Why does service factor matter?
- SF is how much continuous overload the motor can deliver (often 1.15). The drive must cover motor power × SF × application margin, not nameplate HP alone.
- When should I call instead?
- Multi-motor buses, regenerative loads, long motor cables, extreme ambient temperature, or crane duty with unusual overload cycles — call 877-727-8757 for application engineering. This tool returns candidates, not a certified selection.