IAC

VFD Cross-Reference

Enter a variable frequency drive model number and see candidate equivalents across 12 brands (4,034 drives indexed) — matched on voltage class, standard power rating, and overload duty, from official manufacturer ratings tables. Or size a drive from your motor nameplate below. IAC is an authorized distributor for Benshaw, Invertek, LS Electric and Toshiba.

Siemens: 1,506Invertek: 511WEG: 376Benshaw: 316Fuji Electric: 295Yaskawa: 268Allen-Bradley: 245Mitsubishi: 197Toshiba: 129ABB: 111Schneider Electric: 55LS Electric: 25
CIMR-AU4A0362
Yaskawa A1000 · 460V-3ph-in · 160 kW · 304 A · IP00

Invertek equivalents (3)

Toshiba equivalents (1)

  • VFAS3-4160KPCVF-AS3 · 160 kW · 250 HP · 314 A · IP00 · heavy duty · 1190×430×377 mm, 101 kg

Benshaw equivalents (12)

  • MX4PB-HD-200-4-4-HBMX4PB · 200 HP · 240 A · NEMA4/12 · heavy duty · 914.4×762×406.4 mm, 99.8 kg
  • MX4PB-HD-200-4-4-NCMX4PB · 200 HP · 240 A · NEMA4/12 · heavy duty · 914.4×762×406.4 mm, 99.8 kg
  • EMX4e-0352B-V5-C1-HEMX4e · 200 HP · 240 A · IP00 · normal dutynormal duty — verify overload sizing
  • EMX4e-0397B-V5-C1-HEMX4e · 200 HP · 261 A · IP00 · normal dutynormal duty — verify overload sizing
  • EMX4i-0352B-V5-C1-HEMX4i · 200 HP · 240 A · IP00 · normal duty · 523×216×245 mm, 15.5 kgnormal duty — verify overload sizing
  • EMX4i-0397B-V5-C1-HEMX4i · 200 HP · 261 A · IP00 · normal duty · 523×216×245 mm, 15.5 kgnormal duty — verify overload sizing
  • RSi-250-SG-4RSi SG · 160 kW · 250 HP · 325 A · IP00 · normal dutynormal duty — verify overload sizing
  • VFD-RSI-250-H2-4CRSi H2 · 160 kW · 250 HP · 325 A · IP20 · normal duty · 705×380×396 mm, 74.7 kgnormal duty — verify overload sizing
  • MX4PB-SD-200-4-4-HBMX4PB · 200 HP · 240 A · NEMA4/12 · normal duty · 914.4×762×406.4 mm, 99.8 kgnormal duty — verify overload sizing
  • MX4PB-SD-200-4-4-NCMX4PB · 200 HP · 240 A · NEMA4/12 · normal duty · 914.4×762×406.4 mm, 99.8 kgnormal duty — verify overload sizing

ABB equivalents (3)

  • ACS550-U1-290A-4ACS550 · 200 HP · 246 A · NEMA1 · heavy duty · 700×302×400 mm, 69 kg
  • ACS550-01-290A-4ACS550 · 160 kW · 290 A · IP21 · normal duty · 700×302×400 mm, 69 kgnormal duty — verify overload sizing
  • ACS580-01-293A-4ACS580 · 160 kW · 200 HP · 293 A · IP21 · normal duty · 965×300×393 mm, 69 kgnormal duty — verify overload sizing

Fuji Electric equivalents (5)

  • FRN0415E2E-4FRENIC-Ace (E2) · 160 kW · IP00 · heavy duty
  • FRN0415E2S-4FRENIC-Ace (E2) · 160 kW · IP00 · heavy duty
  • FRN0431G2E-4GFRENIC-MEGA (G2) · 160 kW · 250 HP · 325 A · IP00 · heavy duty · 1090.6×530×360 mm, 89 kg
  • FRN0431G2S-4GFRENIC-MEGA (G2) · 160 kW · 250 HP · 325 A · IP00 · heavy duty · 1000×530×360 mm, 89 kg
  • FRN250G1S-4UFRENIC-MEGA (G1S) · 200 HP · 253 A · IP00 · heavy duty · 1000×530×360 mm, 94 kg

WEG equivalents (2)

  • CFW110312T4SZCFW11 · 200 HP · 242 A · IP20 · heavy duty · 1234.4×429.3×360.7 mm, 140.16 kg
  • CFW900F0315T4NB20Y2BCFW900 · 200 HP · 263 A · IP20 · heavy duty · 1074.4×370.8×360.7 mm, 100.97 kg

Mitsubishi equivalents (2)

  • FR-A840-04320FR-A800 · 160 kW · 325 A · IP00 · heavy duty · 1010×498×380 mm, 117 kg
  • FR-F740-160KFR-F700 · 160 kW · 325 A · IP00 · normal duty · 740×465×360 mm, 72 kgnormal duty — verify overload sizing

Candidate matches by voltage class, standard power step and duty; the footprint badge means the candidate fits within the source drive envelope (width and height, ±2 mm, from official dimension tables) — always confirm control features, I/O, and dimensions against the datasheets before substituting. Sources: official manufacturer ratings tables.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs Yaskawa parts — new, refurbished, or exchange units with warranty.

Don't have a drive model? Size from the motor.

Enter nameplate values (or photograph the plate). We size on continuous current (FLA × service factor × duty margin), then list matching VFDs — authorized brands first.

Input phases *

Motor sizing FAQ

What do I read on the nameplate?
Look for horsepower (HP) or kilowatts (kW), full-load amps (FLA or rated current), supply voltage, and service factor (SF). FLA is the most reliable gate for drive current — use it when it is printed.
Why does service factor matter?
SF is how much continuous overload the motor can deliver (often 1.15). The drive must cover motor power × SF × application margin, not nameplate HP alone.
When should I call instead?
Multi-motor buses, regenerative loads, long motor cables, extreme ambient temperature, or crane duty with unusual overload cycles — call 877-727-8757 for application engineering. This tool returns candidates, not a certified selection.