Enter a variable frequency drive model number and see candidate equivalents across 12 brands (4,034 drives indexed) — matched on voltage class, standard power rating, and overload duty, from official manufacturer ratings tables. Or size a drive from your motor nameplate below. IAC is an authorized distributor for Benshaw, Invertek, LS Electric and Toshiba.

Siemens: 1,506Invertek: 511WEG: 376Benshaw: 316Fuji Electric: 295Yaskawa: 268Allen-Bradley: 245Mitsubishi: 197Toshiba: 129ABB: 111Schneider Electric: 55LS Electric: 25
CIMR-AU4A0414
Yaskawa A1000 · 460V-3ph-in · 185 kW · 370 A · IP00

Invertek equivalents (1)

Toshiba equivalents (2)

  • VFAS3-4200KPCVF-AS3 · 200 kW · 300 HP · 387 A · IP00 · heavy duty · 1190×585×377 mm, 134 kg
  • VFAS3-4220KPCVF-AS3 · 220 kW · 350 HP · 427 A · IP00 · heavy duty · 1190×585×377 mm, 136 kg

Benshaw equivalents (4)

  • RSi-350-SG-4RSi SG · 220 kW · 350 HP · 432 A · IP00 · normal dutynormal duty — verify overload sizing
  • VFD-RSI-300-H2-4CRSi H2 · 185 kW · 300 HP · 370 A · IP20 · normal duty · 705×380×396 mm, 74.7 kgnormal duty — verify overload sizing
  • RB2-1-S-302A-15CRB2 · 250 HP · Open Chassis · normal dutynormal duty — verify overload sizing
  • RB3-1-S-302A-15CRB3 · 250 HP · Open Chassis · normal dutynormal duty — verify overload sizing

ABB equivalents (1)

  • ACS580-01-363A-4ACS580 · 200 kW · 300 HP · 363 A · IP21 · normal duty · 955×380×418 mm, 97 kgnormal duty — verify overload sizing

Fuji Electric equivalents (9)

  • FRN0520E2E-4FRENIC-Ace (E2) · 200 kW · IP00 · heavy duty
  • FRN0520E2S-4FRENIC-Ace (E2) · 200 kW · IP00 · heavy duty
  • FRN0547G2E-4GFRENIC-MEGA (G2) · 200 kW · 300 HP · 377 A · IP00 · heavy duty · 1090.6×680×360 mm, 116 kg
  • FRN0547G2S-4GFRENIC-MEGA (G2) · 200 kW · 300 HP · 377 A · IP00 · heavy duty · 1000×680×360 mm, 116 kg
  • FRN0590E2E-4FRENIC-Ace (E2) · 220 kW · IP00 · heavy duty
  • FRN0590E2S-4FRENIC-Ace (E2) · 220 kW · IP00 · heavy duty
  • FRN0610G2E-4GFRENIC-MEGA (G2) · 220 kW · 350 HP · 432 A · IP00 · heavy duty · 1090.6×680×360 mm, 124 kg
  • FRN0610G2S-4GFRENIC-MEGA (G2) · 220 kW · 350 HP · 432 A · IP00 · heavy duty · 1000×680×360 mm, 124 kg
  • FRN300G1S-4UFRENIC-MEGA (G1S) · 250 HP · 304 A · IP00 · heavy duty · 1000×530×360 mm, 98 kg

WEG equivalents (2)

  • CFW110370T4SZCFW11 · 250 HP · 312 A · IP20 · heavy duty · 1234.4×429.3×360.7 mm, 140.16 kg
  • CFW900F0370T4NB20Y2BCFW900 · 250 HP · 315 A · IP20 · heavy duty · 1074.4×370.8×360.7 mm, 100.97 kg

Mitsubishi equivalents (4)

  • FR-A840-04810FR-A800 · 185 kW · 361 A · IP00 · heavy duty · 1010×498×380 mm, 117 kg
  • FR-A840-05470FR-A800 · 220 kW · 432 A · IP00 · heavy duty · 1010×680×380 mm, 166 kg
  • FR-F740-185KFR-F700 · 185 kW · 361 A · IP00 · normal duty · 300×220×190 mm, 7.5 kgnormal duty — verify overload sizing
  • FR-F740-220KFR-F700 · 220 kW · 432 A · IP00 · normal duty · 1010×498×380 mm, 110 kgnormal duty — verify overload sizing

Candidate matches by voltage class, standard power step and duty; the footprint badge means the candidate fits within the source drive envelope (width and height, ±2 mm, from official dimension tables) — always confirm control features, I/O, and dimensions against the datasheets before substituting. Sources: official manufacturer ratings tables.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs Yaskawa parts — new, refurbished, or exchange units with warranty.

Don't have a drive model? Size from the motor.

Enter nameplate values (or photograph the plate). We size on continuous current (FLA × service factor × duty margin), then list matching VFDs — authorized brands first.

Input phases *

Motor sizing FAQ

What do I read on the nameplate?
Look for horsepower (HP) or kilowatts (kW), full-load amps (FLA or rated current), supply voltage, and service factor (SF). FLA is the most reliable gate for drive current — use it when it is printed.
Why does service factor matter?
SF is how much continuous overload the motor can deliver (often 1.15). The drive must cover motor power × SF × application margin, not nameplate HP alone.
When should I call instead?
Multi-motor buses, regenerative loads, long motor cables, extreme ambient temperature, or crane duty with unusual overload cycles — call 877-727-8757 for application engineering. This tool returns candidates, not a certified selection.