IAC

VFD Cross-Reference

Enter a variable frequency drive model number and see candidate equivalents across 12 brands (4,034 drives indexed) — matched on voltage class, standard power rating, and overload duty, from official manufacturer ratings tables. Or size a drive from your motor nameplate below. IAC is an authorized distributor for Benshaw, Invertek, LS Electric and Toshiba.

Siemens: 1,506Invertek: 511WEG: 376Benshaw: 316Fuji Electric: 295Yaskawa: 268Allen-Bradley: 245Mitsubishi: 197Toshiba: 129ABB: 111Schneider Electric: 55LS Electric: 25
CIMR-JU4A0005BAA
Yaskawa J1000 · 460V-3ph-in · 1.5 kW · 4.8 A · IP20 · 128×108×154 mm, 1.7 kg

Invertek equivalents (13)

LS Electric equivalents (1)

  • 0015H100-4H100 · 1.5 kW · 2 HP · 4 A · IP20 · normal duty · 232×160×181 mm, 3.3 kglarger: +52mm W / +104mm H / +27mm Dnormal duty — verify overload sizing

Toshiba equivalents (5)

  • VFAS3-4015PCVF-AS3 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 326×130×202 mm, 4.5 kglarger: +22mm W / +198mm H / +48mm D
  • VFMB1-4015PLVF-MB1 · 1.5 kW · 4.1 A · IP20 · heavy duty · 270×45×232 mm, 1.9 kglarger: +142mm H / +78mm D
  • VFS15-4015PL-WVF-S15 · 1.5 kW · 4.1 A · IP20 · heavy duty · 130×107×153 mm, 1.5 kgfits footprint
  • VFS15-4015PL-W1VF-S15 · 1.5 kW · 4.1 A · IP20 · heavy duty · 130×107×153 mm, 1.5 kgfits footprint
  • VFS15-4015PL1-W1VF-S15 · 1.5 kW · 4.1 A · IP20 · heavy duty · 130×105×150 mm, 1.3 kgfits footprint

Benshaw equivalents (1)

  • RSI-002-GM2-4CRSi GM2 · 1.5 kW · 2 HP · 3.1 A · IP20 · normal duty · 154×86.2×131.5 mm, 1.08 kglarger: +26mm Hnormal duty — verify overload sizing

Allen-Bradley equivalents (9)

  • 22A-D4P0F104PowerFlex 4 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 152×80×136 mm, 1.4 kglarger: +24mm H
  • 22A-D4P0N104PowerFlex 4 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 152×80×136 mm, 1.4 kglarger: +24mm H
  • 22B-D4P0F104PowerFlex 40 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 180×100×136 mm, 2.2 kglarger: +52mm H
  • 22B-D4P0N104PowerFlex 40 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 180×100×136 mm, 2.2 kglarger: +52mm H
  • 25A-D4P0N104PowerFlex 523 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 152×72×172 mm, 1.1 kglarger: +24mm H / +18mm D
  • 25A-D4P0N114PowerFlex 523 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 152×72×172 mm, 1.1 kglarger: +24mm H / +18mm D
  • 25B-D4P0N104PowerFlex 525 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 152×72×172 mm, 1.1 kglarger: +24mm H / +18mm D
  • 25B-D4P0N114PowerFlex 525 · 1.5 kW · 2 HP · 4 A · IP20 · heavy duty · 152×72×172 mm, 1.1 kglarger: +24mm H / +18mm D
  • 22B-D4P0C104PowerFlex 40 · 1.5 kW · 2 HP · 4 A · IP66 · heavy duty · 180×100×136 mm, 2.2 kglarger: +52mm H

ABB equivalents (3)

  • ACS550-01-04A1-4ACS550 · 1.5 kW · 2 HP · 4.1 A · IP21 · normal duty · 330×125×212 mm, 6.5 kglarger: +17mm W / +202mm H / +58mm Dnormal duty — verify overload sizing
  • ACS580-01-04A0-4ACS580 · 1.5 kW · 2 HP · 4 A · IP21 · normal duty · 330×125×210 mm, 4.5 kglarger: +17mm W / +202mm H / +56mm Dnormal duty — verify overload sizing
  • ACS550-U1-04A1-4ACS550 · 1.5 kW · 2 HP · 4.1 A · NEMA1 · normal duty · 330×125×212 mm, 6.5 kglarger: +17mm W / +202mm H / +58mm Dnormal duty — verify overload sizing

Fuji Electric equivalents (8)

  • FRN0004G2E-4GFRENIC-MEGA (G2) · 1.5 kW · 2 HP · 4.2 A · IP20 · heavy duty · 260×150×145 mm, 2.8 kglarger: +42mm W / +132mm H
  • FRN0004G2S-4GFRENIC-MEGA (G2) · 1.5 kW · 2 HP · 4.2 A · IP20 · heavy duty · 260×150×145 mm, 2.6 kglarger: +42mm W / +132mm H
  • FRN0005C2E-4FRENIC-Mini (C2) · 1.5 kW · 2 HP · 4.3 A · IP20 · heavy duty · 245×140×182 mm, 3 kglarger: +32mm W / +117mm H / +28mm D
  • FRN0005C2S-4FRENIC-Mini (C2) · 1.5 kW · 2 HP · 4.3 A · IP20 · heavy duty · 130×110×139 mm, 1.7 kgfits footprint
  • FRN0006E2E-4FRENIC-Ace (E2) · 1.5 kW · 2 HP · IP20 · heavy duty
  • FRN0006E2S-4FRENIC-Ace (E2) · 1.5 kW · 2 HP · IP20 · heavy duty
  • FRN002E1S-4UFRENIC-Multi (E1S) · 2 HP · 3.7 A · IP20 · heavy duty · 130×110×150 mmfits footprint
  • FRN002G1S-4UFRENIC-MEGA (G1S) · 2 HP · 4 A · IP20 · heavy duty · 260×150×145 mm, 2.6 kglarger: +42mm W / +132mm H

Schneider Electric equivalents (2)

  • ATV320U15N4BAltivar Machine ATV320 · 1.5 kW · 2 HP · 4.1 A · IP20 · heavy duty · 325×45×245 mm, 2.5 kglarger: +197mm H / +91mm D
  • ATV320U15N4CAltivar Machine ATV320 · 1.5 kW · 2 HP · 4.1 A · IP20 · heavy duty · 143×105×158 mm, 1.3 kglarger: +15mm H / +4mm D

WEG equivalents (6)

  • CFW320A03P5T4NB20CFW320 · 2 HP · 3.5 A · IP20 · heavy duty · 157.9×70×148.4 mm, 0.9 kglarger: +30mm H
  • CFW320B03P5T4DB20CFW320 · 2 HP · 3.5 A · IP20 · heavy duty · 198.9×70×158.4 mm, 1.34 kglarger: +71mm H / +4mm D
  • CFW900A03P6T4DB20Y2BCFW900 · 2 HP · 2.8 A · IP20 · heavy duty · 269.2×144.8×221 mm, 4.49 kglarger: +37mm W / +141mm H / +67mm D
  • CFW900A04P8T4DB20Y2BCFW900 · 2 HP · 3.9 A · IP20 · heavy duty · 269.2×144.8×221 mm, 4.49 kglarger: +37mm W / +141mm H / +67mm D
  • CFW110003T4O55DSZCFW11 · 2 HP · 3.6 A · IP55 · heavy duty · 528.3×271.8×279.4 mm, 17.01 kglarger: +164mm W / +400mm H / +125mm D
  • CFW110003T4ON1ZCFW11 · 2 HP · 3.6 A · NEMA1 · heavy duty · 307.3×147.3×228.6 mm, 9.98 kglarger: +39mm W / +179mm H / +75mm D

Mitsubishi equivalents (7)

  • FR-A840-00052FR-A800 · 1.5 kW · 4 A · IP20 · heavy duty · 260×150×140 mm, 3 kglarger: +42mm W / +132mm H
  • FR-D740-1.5KFR-D700 · 1.5 kW · 3.6 A · IP20 · heavy duty · 128×108×135.5 mm, 1.4 kgfits footprint
  • FR-E740-1.5KFR-E700 · 1.5 kW · 4 A · IP20 · heavy duty · 150×140×135 mm, 1.9 kglarger: +32mm W / +22mm H
  • FR-E840-0040FR-E800 · 1.5 kW · 4 A · IP20 · heavy duty · 128×108×135 mm, 1.4 kgfits footprint
  • FR-E840-1.5KNCFR-E800 · 1.5 kW · 4 A · IP20 · heavy duty · 128×108×162.6 mm, 1.4 kgfits footprint
  • FR-E846-0040FR-E800 · 1.5 kW · 4 A · IP66/IP67 · heavy duty · 200×390×156 mm, 5.9 kglarger: +282mm W / +72mm H
  • FR-F740-1.5KFR-F700 · 1.5 kW · 3.5 A · IP20 · normal duty · 260×150×140 mm, 3.5 kglarger: +42mm W / +132mm Hnormal duty — verify overload sizing

Siemens equivalents (54)

Candidate matches by voltage class, standard power step and duty; the footprint badge means the candidate fits within the source drive envelope (width and height, ±2 mm, from official dimension tables) — always confirm control features, I/O, and dimensions against the datasheets before substituting. Sources: official manufacturer ratings tables.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs Yaskawa parts — new, refurbished, or exchange units with warranty.

Don't have a drive model? Size from the motor.

Enter nameplate values (or photograph the plate). We size on continuous current (FLA × service factor × duty margin), then list matching VFDs — authorized brands first.

Input phases *

Motor sizing FAQ

What do I read on the nameplate?
Look for horsepower (HP) or kilowatts (kW), full-load amps (FLA or rated current), supply voltage, and service factor (SF). FLA is the most reliable gate for drive current — use it when it is printed.
Why does service factor matter?
SF is how much continuous overload the motor can deliver (often 1.15). The drive must cover motor power × SF × application margin, not nameplate HP alone.
When should I call instead?
Multi-motor buses, regenerative loads, long motor cables, extreme ambient temperature, or crane duty with unusual overload cycles — call 877-727-8757 for application engineering. This tool returns candidates, not a certified selection.